Component
|
Problem
|
Source of Problem
|
Solution
|
Basic
|
No power
|
Nut & bolt connections at battery and back of inverter / charger may be loose
|
Check all connections and tighten
|
|
|
Plug into battery charger may have come loose
|
Reinsert
|
|
|
Powerstrip
|
Check that it is connected to inverter and set to ON
|
Component
|
Problem
|
Source of Problem
|
Solution
|
Battery
|
Not powering equipment
|
Low voltage <11 volts or no reading at all
|
Check volt reading on volt meter. If <11v, recharge battery w/separate charger beyond 11.5v. If no reading, check that cables are connected to battery.
|
|
|
If less than 11 volts, charger will NOT work in the 750 or 1250 watt inverters.
|
Recharge battery with separate charger beyond 11v.
|
|
|
Positive and negative cables may have been incorrectly installed - thus damaging cells in battery.
|
May need to replace battery.
|
|
|
Positive and negative cables may have been incorrectly installed - thus damaging cells in battery.
|
May need to replace battery.
|
|
|
Check that power in building does not get turned off overnight during recharging period.
|
|
|
|
Check battery casing for damage or terminal residue.
|
May need to replace battery.
|
|
|
Multiple batteries not connected correctly.
|
Check that cables are connected in parallel, positive to positive, and negative to negatve.
|
|
|
Has been used for 250+ full cycles.
|
May need to replace battery.
|
Component
|
Problem
|
Source of Problem
|
Solution
|
Curtis Meter
|
No Lights on Display
|
Wires not connected properly.
|
Red wire plugs into #1 on meter, and attaches to + on battery.
Green wire plugs into #4 on meter and attaches to + on battery.
Black wire plugs into #2 on meter and attaches to - on battery.
Nothing is attached to #3.
|
|
Flashing Red (2nd to last bar)
|
Battery voltage getting low (70% duscharged).
|
Charge batteries.
|
|
Flashing Red (Last bar, alternately with 2nd to last bar)
|
Battery voltage almost empty (80% discharged).
|
Charge batteries.
|